Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00726
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2007 | CRAIG GROSS | ZONING | REVIEW | Approved | |
| 03/23/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/23/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003. 2. The minimum occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2003 or an approved statistical analysis of the specific occupancy type. Reference Section 403.3, IMC 2003. 3. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2003. |
| 03/27/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 03/27/2007 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 03/27/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |