Permit Number: T07CM00726
Parcel: 10605001B

Address:
3971 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00726
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
03/15/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Second request. Provide mechanical plan including calculations to show that the new area has adequate ventilation per section 403, IMC 2003.
03/15/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00726 3/15/07

1. SECOND REQUEST. Per Mechanical comment, reflect any such changes on Electrical plans, as applicable.
03/15/2007 MARTIN BROWN FIRE REVIEW Approved
03/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide cleanouts per Sections 707.4 and 707.11, UPC 2003.
03/23/2007 GBONILL1 WWM REVIEW Needs Review
03/23/2007 GBONILL1 ZONING REVIEW Needs Review
03/23/2007 ROBERT SHERRY WATER REVIEW Approved
03/23/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review