Permit Number: T07CM00726
Parcel: 10605001B

Address:
3971 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00726
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
03/02/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE CLEAR CODE ANALYSIS ON PLANS OR CITY CODE ANALYSIS DATA SHEET. INDICATE NEW FLOOR AREA OF TOTAL A-2 OCCUPANCY AND NEW OCCUPANT LOAD.

2) JUSTIFY "EXISTING ADA RESTROOMS". THEY DO NOT APPEAR TO MEET THE 2003 ANSI 117.1 REQUIREMENTS.

3) YOU MAY NOT ATTACH PARTITIONS TO SUSPENDED CEILINGS WITHOUT STRUCTURAL ANALYSIS . REFERENCE 2/A5

4) WHAT IS FIRE CHALK? REFERENCE 1/A5.

5) WHY DOES FLOOR PLAN HAVE REFERENCES TO CARS?
03/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide mechanical plan including calculations to show that the new area has adequate ventilation per section 403, IMC 2003.
03/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00726 3/2/07

1. The branch circuit feeding the exit sign shall be the same branch circuit as the other lighting in the area. Reference NEC 700.12 (E).
2. Per Mechanical comment, reflect any such changes on Electrical plans, as applicable.
03/15/2007 GBONILL1 WATER REVIEW Needs Review
03/15/2007 GBONILL1 ZONING REVIEW Needs Review
03/15/2007 GBONILL1 WWM REVIEW Needs Review
03/15/2007 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
03/15/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/15/2007 GBONILL1 FIRE REVIEW Needs Review