Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00726
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/23/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
03/02/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CLEAR CODE ANALYSIS ON PLANS OR CITY CODE ANALYSIS DATA SHEET. INDICATE NEW FLOOR AREA OF TOTAL A-2 OCCUPANCY AND NEW OCCUPANT LOAD. 2) JUSTIFY "EXISTING ADA RESTROOMS". THEY DO NOT APPEAR TO MEET THE 2003 ANSI 117.1 REQUIREMENTS. 3) YOU MAY NOT ATTACH PARTITIONS TO SUSPENDED CEILINGS WITHOUT STRUCTURAL ANALYSIS . REFERENCE 2/A5 4) WHAT IS FIRE CHALK? REFERENCE 1/A5. 5) WHY DOES FLOOR PLAN HAVE REFERENCES TO CARS? |
03/02/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide mechanical plan including calculations to show that the new area has adequate ventilation per section 403, IMC 2003. |
03/02/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00726 3/2/07 1. The branch circuit feeding the exit sign shall be the same branch circuit as the other lighting in the area. Reference NEC 700.12 (E). 2. Per Mechanical comment, reflect any such changes on Electrical plans, as applicable. |
03/15/2007 | GBONILL1 | WATER | REVIEW | Needs Review | |
03/15/2007 | GBONILL1 | ZONING | REVIEW | Needs Review | |
03/15/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
03/15/2007 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
03/15/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
03/15/2007 | GBONILL1 | FIRE | REVIEW | Needs Review |