Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00725
Parcel: 110101150

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T07CM00725
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2007 SUZANNE BOHNET ENGINEERING REVIEW Approved
03/05/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T07CM00725

4/13/07 2952 N. ST. AUGUSTINE PLACE

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM
IF IT EXISTS.

FOUNDATION PLANS:

1. PLEASE PROVIDE THE ALLOWABLE SOIL BEARING CAPACITY USED. SEE R401.4


FLOOR PLANS:

1. PLEASE PROVIDE THE SIZE OF THE GLASS BLOCK WINDOW IN THE BATH ROOM.

2. LOCATE THE BRACED WALL PANELS.

3. PLEASE DIMENSION THE HEARTH EXTENSION OF THE FIREPLACE. ALSO, PROVIDE A CROSS SECTION OF THE INSTALLATION.


STRUCTURAL PLANS:

1. ROOF PLAN / S-1 ; PLEASE LIGHTEN THE DETAIL NUMBERS FOR CLARITY.

SECTIONS - DETAILS - MISC. NOTES:

1. 5 / S-2 ; PLEASE SPECIFY THE SIMPSON POST BASE. DOES IT RAISE THE END GRAIN 1" ABOVE THE CONCRETE? SEE R319.1.4 EXC. 1 .

2. 1 / S-3 ; PLEASE SPECIFY THE WALL AND CEILING GWB. SEE TABLE R702.3.5 FOOTNOTE d

3. 2 / S-3 ; PLEASE SPECIFY THE STUD / LEDGER CONNECTION.

4. 3 / S-3 ; PROVIDE THE STUD / LEDGER CONNECTION.

5. 3 / S-3 ; PLEASE LOCATE THE 6X10.

6. 3 / S-3 ; PLEASE SPEC THE WALL AND CEILING GWB. SEE TABLE R702.3.5 FOOTNOTE d

7. 4 / S-3 ; SIMPSON DOESN'T LIST A VALUE FOR AN A35 IN THIS CONFIGURATION.

8. 4 / S-3 ; PLEASE SPECIFY THE POST CAP.

9. 4 / S-4 ; THE 16d @ EACH JOIST FOR THE PLATE / ROOF CONNECTION IS OVER SPACED. SEE TABLE R602.3(2).

10. S-4 ; PLEASE USE THE 2003 IRC.

PLUMBING PLANS:

1. PLEASE CHECK THE NUMBER OF FIXTURE UNITS PER APPLIANCE WITH THE 2003 UPC.

2. JUSTIFY THE EXISTING WATER DISTRIBUTION SYSTEM'S ABILITY TO SUPPLY BOTH THE EXISTING AND THE PROPOSED FIXTURE UNITS.

3. PROVIDE THE HEIGHT OF THE TPR LINE ABOVE GRADE. SEE UPC 608.5 .

ELECTRICAL PLANS:

1. THE WORKING AREA AROUND THE SUB-PANEL APPEARS TO BE LESS THAN REQUIRED BY FIGURE E3305.1 .




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 837-4910



PLAN CHECK COMMENTS - PROJECT #T07CM00725

4/13/07 2952 N. ST. AUGUSTINE PLACE

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM
IF IT EXISTS.

FOUNDATION PLANS:

1. PLEASE PROVIDE THE ALLOWABLE SOIL BEARING CAPACITY USED. SEE R401.4


FLOOR PLANS:

1. PLEASE PROVIDE THE SIZE OF THE GLASS BLOCK WINDOW IN THE BATH ROOM.

2. LOCATE THE BRACED WALL PANELS.

3. PLEASE DIMENSION THE HEARTH EXTENSION OF THE FIREPLACE. ALSO, PROVIDE A CROSS SECTION OF THE INSTALLATION.


STRUCTURAL PLANS:

1. ROOF PLAN / S-1 ; PLEASE LIGHTEN THE DETAIL NUMBERS FOR CLARITY.

SECTIONS - DETAILS - MISC. NOTES:

1. 5 / S-2 ; PLEASE SPECIFY THE SIMPSON POST BASE. DOES IT RAISE THE END GRAIN 1" ABOVE THE CONCRETE? SEE R319.1.4 EXC. 1 .

2. 1 / S-3 ; PLEASE SPECIFY THE WALL AND CEILING GWB. SEE TABLE R702.3.5 FOOTNOTE d

3. 2 / S-3 ; PLEASE SPECIFY THE STUD / LEDGER CONNECTION.

4. 3 / S-3 ; PROVIDE THE STUD / LEDGER CONNECTION.

5. 3 / S-3 ; PLEASE LOCATE THE 6X10.

6. 3 / S-3 ; PLEASE SPEC THE WALL AND CEILING GWB. SEE TABLE R702.3.5 FOOTNOTE d

7. 4 / S-3 ; SIMPSON DOESN'T LIST A VALUE FOR AN A35 IN THIS CONFIGURATION.

8. 4 / S-3 ; PLEASE SPECIFY THE POST CAP.

9. 4 / S-4 ; THE 16d @ EACH JOIST FOR THE PLATE / ROOF CONNECTION IS OVER SPACED. SEE TABLE R602.3(2).

10. S-4 ; PLEASE USE THE 2003 IRC.

PLUMBING PLANS:

1. PLEASE CHECK THE NUMBER OF FIXTURE UNITS PER APPLIANCE WITH THE 2003 UPC.

2. JUSTIFY THE EXISTING WATER DISTRIBUTION SYSTEM'S ABILITY TO SUPPLY BOTH THE EXISTING AND THE PROPOSED FIXTURE UNITS.

3. PROVIDE THE HEIGHT OF THE TPR LINE ABOVE GRADE. SEE UPC 608.5 .

ELECTRICAL PLANS:

1. THE WORKING AREA AROUND THE SUB-PANEL APPEARS TO BE LESS THAN REQUIRED BY FIGURE E3305.1 .




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 837-4910
03/05/2007 TERRY STEVENS ZONING REVIEW Approved
03/05/2007 TERRY STEVENS NPPO REVIEW Passed
03/07/2007 GERRY KOZIOL WWM REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/07/2007 FSANCHE1 OUT TO CUSTOMER Completed