Permit Number: T07CM00716
Parcel: 11522002A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T07CM00716
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2007 MARTIN BROWN FIRE REVIEW Approved
03/09/2007 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/09/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied March 7, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: First Tee Clubhouse
CITY OF TUCSON LOG NO. T07CM00716
WILLDAN PROJECT NO. 13881-7026 – 1ST REVIEW

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IBC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC with local modifications, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Martin Haeberle.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
A3 231 VB 5356 yes yes

Special Inspection is required for the following items:
Concrete
Welding
Adhesive anchors
Site preparation

The following items are acceptable for deferred submittals:
I joists

GENERAL COMMENTS:
General
A signed special inspection form from the City of Tucson is required at the time that the plans are resubmitted for a back check. Reference the City of Tucson Submittal Policy.

A deferred submittal letter for I-joists will need to be forwarded directly to the Building Official and approved prior to the plans being delivered to the City. Reference the City of Tucson Submittal Policy.

ARCHITECTURAL COMMENTS:
Sheet T1.1
Please provide code analysis data on plans including building type, occupancy, occupant load, and square footage including all roofed area. Reference section 106.1 IBC.

Provide a complete site plan indicating all accessibility requirements, building sewer plans and specifications, water supply and electrical service for the proposed project or the civil drawings that would have all this pertinent data.

Sheet A1.1
Additional exits are required for the multi-purpose room for when the accordion doors are closed. Reference Table 1014.1 IBC.

Doors exiting the multi-purpose room encroach more than half the required width in the hallways. Reference section 1005.2 IBC.

The plans provided do not include the required service sink and drinking fountain per Table 2902.1 IBC. Revise plans and include details for the accessible drinking fountain.

Revise code references to the 2003 IBC as adopted by the city of Tucson.

Sheet A2.1
Walls within the toilet room are to have non-absorbent surfaces as specified by section 1210.2 IBC. Note: Paint is not accepted by the City of Tucson for compliance with this section.

Specify on plans the required toe clearance for the partitions per section 604.8.5 A117.1 ANSI.

Sheet A4.1
Revise room finish requirements for the toilet rooms per section 1210.2 IBC.

The hardware set indications are missing from the door schedule. Please revise. Reference section 106.1 IBC.

The door to remain unlocked while occupied sign is an exception allowed for the main exit only. Please revise plan to show panic hardware for all other exits as required per section 1008.1.9 IBC.

Reflect on plans the required u value for windows and doors per the energy compliance certificate.

Detail 2 does not show the required flashing, anchoring, and weather protection for the proposed slum block veneer. Reference Sections 1405.3 and 1405.5 IBC.

Sheet A5.1
The plans do not show the required weep screed for the stucco system. Reference section 2512.2 IBC. Show how this is to be accomplished per manufacturer’s installation requirements.

The Veranda is indicated as an open truss, but weather protection is not being provided into the conditioned space. See detail 6. Reference section 1405.2 IBC.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Sheet P1
Revise plumbing plans to include additional fixtures required per table 2902.1 IBC. See architectural comments.

Sheet P2
Revise plans to reference the adopted codes of the City of Tucson.

Include in plans and specifications water line/loss calculations for the proposed project per City of Tucson Submittal Requirements.

Please complete the data information for the requirement of a backwater valve. Reference section 106.1 IBC

MECHANICAL COMMENTS:
Sheet M1
Please clarify outside air calculations for the multi-purpose/meeting room. It does not appear to comply with Table 403.3 IMC. Note: If ASHRAE 61.1 is to be used, provide justification for factors being used.

ELECTRICAL COMMENTS:
Reviewed and accepted.

ENERGY CODE COMMENTS:
See architectural comments.

ACCESSIBILITY COMMENTS:
See architectural comments.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb
03/09/2007 WILLDAN ADA REVIEW Denied March 7, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: First Tee Clubhouse
CITY OF TUCSON LOG NO. T07CM00716
WILLDAN PROJECT NO. 13881-7026 – 1ST REVIEW

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IBC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC with local modifications, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Martin Haeberle.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
A3 231 VB 5356 yes yes

Special Inspection is required for the following items:
Concrete
Welding
Adhesive anchors
Site preparation

The following items are acceptable for deferred submittals:
I joists

GENERAL COMMENTS:
General
A signed special inspection form from the City of Tucson is required at the time that the plans are resubmitted for a back check. Reference the City of Tucson Submittal Policy.

A deferred submittal letter for I-joists will need to be forwarded directly to the Building Official and approved prior to the plans being delivered to the City. Reference the City of Tucson Submittal Policy.

ARCHITECTURAL COMMENTS:
Sheet T1.1
Please provide code analysis data on plans including building type, occupancy, occupant load, and square footage including all roofed area. Reference section 106.1 IBC.

Provide a complete site plan indicating all accessibility requirements, building sewer plans and specifications, water supply and electrical service for the proposed project or the civil drawings that would have all this pertinent data.

Sheet A1.1
Additional exits are required for the multi-purpose room for when the accordion doors are closed. Reference Table 1014.1 IBC.

Doors exiting the multi-purpose room encroach more than half the required width in the hallways. Reference section 1005.2 IBC.

The plans provided do not include the required service sink and drinking fountain per Table 2902.1 IBC. Revise plans and include details for the accessible drinking fountain.

Revise code references to the 2003 IBC as adopted by the city of Tucson.

Sheet A2.1
Walls within the toilet room are to have non-absorbent surfaces as specified by section 1210.2 IBC. Note: Paint is not accepted by the City of Tucson for compliance with this section.

Specify on plans the required toe clearance for the partitions per section 604.8.5 A117.1 ANSI.

Sheet A4.1
Revise room finish requirements for the toilet rooms per section 1210.2 IBC.

The hardware set indications are missing from the door schedule. Please revise. Reference section 106.1 IBC.

The door to remain unlocked while occupied sign is an exception allowed for the main exit only. Please revise plan to show panic hardware for all other exits as required per section 1008.1.9 IBC.

Reflect on plans the required u value for windows and doors per the energy compliance certificate.

Detail 2 does not show the required flashing, anchoring, and weather protection for the proposed slum block veneer. Reference Sections 1405.3 and 1405.5 IBC.

Sheet A5.1
The plans do not show the required weep screed for the stucco system. Reference section 2512.2 IBC. Show how this is to be accomplished per manufacturer’s installation requirements.

The Veranda is indicated as an open truss, but weather protection is not being provided into the conditioned space. See detail 6. Reference section 1405.2 IBC.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Sheet P1
Revise plumbing plans to include additional fixtures required per table 2902.1 IBC. See architectural comments.

Sheet P2
Revise plans to reference the adopted codes of the City of Tucson.

Include in plans and specifications water line/loss calculations for the proposed project per City of Tucson Submittal Requirements.

Please complete the data information for the requirement of a backwater valve. Reference section 106.1 IBC

MECHANICAL COMMENTS:
Sheet M1
Please clarify outside air calculations for the multi-purpose/meeting room. It does not appear to comply with Table 403.3 IMC. Note: If ASHRAE 61.1 is to be used, provide justification for factors being used.

ELECTRICAL COMMENTS:
Reviewed and accepted.

ENERGY CODE COMMENTS:
See architectural comments.

ACCESSIBILITY COMMENTS:
See architectural comments.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb
03/14/2007 GERRY KOZIOL WWM REVIEW Denied NEEDS TO SHOW METHOD/CONNECTION TO PUBLIC SEWER.
03/19/2007 ROBERT SHERRY WATER REVIEW Denied Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 2003.
03/27/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: First Tee Clubhouse - El Rio Golf Course
T07CM00716
Site Plan (1st Review)

TRANSMITTAL DATE: March 27, 2007

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Provide a copy of the last approved site plan.

2. This project requires a site plan review. If this project is a less than 25% expansion a partial site plan may be provided. This site plan will meet the minimum requirements of Development Standards 2-02. Show all calculations on the plan to include building expansion.

3. Additional comments maybe forth coming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\site\t07cm00716.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
03/29/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: March 29, 2007
ACTIVITY NUMBER: T07CM00716
PROJECT NAME: First Tee Clubhouse El Rio Golf Course
PROJECT ADDRESS: 1400 West Speedway Blvd.
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

1. This project requires a site review. Submit the last approved site plan and a revise site plan that meets Development Standard 2-02, Site Plan Content and Specifications. Please refer to the Zoning Review comment 2. Due to the fact this project appears to be minimal the site plan review may be able to be accomplished over the counter.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/03/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
04/03/2007 SHANAE POWELL REJECT SHELF Completed