Permit Number: T07CM00713
Parcel: 11921040C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM00713
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2007 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/09/2007 WILLDAN ADA REVIEW Denied March 6, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Kennedy's Comfort Station Renovation
CITY OF TUCSON LOG NO. T07CM00713
WILLDAN PROJECT NO. 13881-7027 – 1ST REVIEW

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IBC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC with local modifications, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Martin Haeberle.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
U NA VB 273 No No

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
Reviewed and accepted.

ARCHITECTURAL COMMENTS:
Sheet A1.1
Include in plans a structural detail for the load transfer of the glulam beam thru the masonry wall. Reference section 106.1 IBC.

Provide a detail for the ramp/curb cut for the proposed new accessible route. Reference the City of Tucson design standards.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Reviewed and accepted,

MECHANICAL COMMENTS:
Reviewed and accepted.

ELECTRICAL COMMENTS:
Reviewed and accepted.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb
03/09/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied March 6, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Kennedy's Comfort Station Renovation
CITY OF TUCSON LOG NO. T07CM00713
WILLDAN PROJECT NO. 13881-7027 – 1ST REVIEW

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IBC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC with local modifications, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Martin Haeberle.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
U NA VB 273 No No

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
Reviewed and accepted.

ARCHITECTURAL COMMENTS:
Sheet A1.1
Include in plans a structural detail for the load transfer of the glulam beam thru the masonry wall. Reference section 106.1 IBC.

Provide a detail for the ramp/curb cut for the proposed new accessible route. Reference the City of Tucson design standards.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Reviewed and accepted,

MECHANICAL COMMENTS:
Reviewed and accepted.

ELECTRICAL COMMENTS:
Reviewed and accepted.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb
03/29/2007 DAVID RIVERA ZONING REVIEW Denied 03/30/07

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The site plan has been reviewed by Zoning Review Section but cannot approve the plan until the following zoning comments are addressed.

2. Label the maximum slope allowed for handicapped parking spaces and access aisle that serve the parking spaces. The maximum slope allowed per ANSI section 503.4 is 1:48 (2%). Label the slope on the handicapped parking space detail and access aisle.

3. Truncated domes are required at all access ramps and at areas where the sidewalk is flush and transitions from the sidewalk to the vehicular use areas. This includes at the H.C. access aisle that transitions from the sidewalk onto the aisle.

4. Zoning will re-review the plan on the next submittal to ensure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

5. Zoning is willing to re-review and approve the changes to plan over the counter on the next submittal. If you wish to do so please call in advance for an appointment. 837-4957

Final Status

Task End Date Reviewer's Name Type of Review Description
04/02/2007 SUE REEVES OUT TO CUSTOMER Completed
04/02/2007 SUE REEVES REJECT SHELF Completed