Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2007 TERRY STEVENS ZONING REVIEW Approved
03/07/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm00683 3/7/07

1. Tallys on panel phases A and B appear to be 16.25 KW and 22.25 KW respectively, not 11.15 KW. Amps appear to exceed the capacity of the panel.
2. Minimum font size 1/8".
3. Provide a disconnecting means for EF-2. Reference NEC 430 Part IX.