Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM00683
Parcel: 140200250

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM00683
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2007 TERRY STEVENS ZONING REVIEW Approved
03/07/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm00683 3/7/07

1. Tallys on panel phases A and B appear to be 16.25 KW and 22.25 KW respectively, not 11.15 KW. Amps appear to exceed the capacity of the panel.
2. Minimum font size 1/8".
3. Provide a disconnecting means for EF-2. Reference NEC 430 Part IX.
03/07/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
03/15/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/15/2007 CAGUILA1 WWM REVIEW Needs Review