| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 03/07/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t07cm00683 3/7/07 1. Tallys on panel phases A and B appear to be 16.25 KW and 22.25 KW respectively, not 11.15 KW. Amps appear to exceed the capacity of the panel. 2. Minimum font size 1/8". 3. Provide a disconnecting means for EF-2. Reference NEC 430 Part IX. |
| 03/07/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/15/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 03/15/2007 | CAGUILA1 | WWM | REVIEW | Needs Review |