The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T07CM00682
Parcel: 11105245C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00682
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2007 TERRY STEVENS ZONING REVIEW Approved
02/21/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/21/2007 MARTIN BROWN FIRE REVIEW Approved
02/27/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
2. Provide the listing for the two-way cleanout fitting called out in detail 2/P1.1. Reference Sections 103.2.3 and 707.6, UPC 2003.
3. Specify the materials to be used for the drainage piping and fittings. Reference Section 701.0, UPC 2003.
4. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length. Reference Section 707.4, UPC 2003.
5. Specify lavatory faucets that are designed to ARS Title 45, Chapter 1, Article 12. The maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. Reference Section 402.1, UPC 2003, as amended by the State of Arizona.
6. Provide fixture descriptions for all plumbing fixtures. Reference Section 401.1, UPC 2003.
02/27/2007 ROBERT SHERRY WATER REVIEW Approved
02/27/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
02/27/2007 FSANCHE1 WWM REVIEW Needs Review
02/27/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/27/2007 FSANCHE1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2007 FSANCHE1 OUT TO CUSTOMER Completed