Permit Number: T07CM00679
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00679
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2007 STEVE SHIELDS ZONING REVIEW Approved
02/21/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Specify the insulation for the new ductwork.
2. Show how recirculation of air from the restroom is to be prevented. Reference Section 403.2, IMC 2003.
02/21/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied
02/21/2007 ROBERT SHERRY WATER REVIEW Approved
02/21/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1)PROVIDE ACCESSIBILITY CLEARANCES PER TABLE 404.2.3.1 ANSI A117.1 2003 FOR DOOR IN HALL LEADING TO RESTROOM FACILITIES.
02/21/2007 JASON GREEN ENGINEERING REVIEW Approved
02/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a waste and vent riser diagram to clarify the revisions shown in the plumbing plan.
2. Plumbing keynote 3 indicates that hot water is being supplied. Show the source of the hot water and indicate how the temperature of hot water to the lavatory is to be limited to 110 degree Fahrenheit.
02/21/2007 MARTIN BROWN FIRE REVIEW Approved
02/23/2007 DROBEY1 WWM REVIEW Needs Review
02/23/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/23/2007 DELMA ROBEY APPROVAL SHELF Completed
02/23/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/23/2007 DELMA ROBEY REJECT SHELF Completed