Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00668
Parcel: 117101280

Address:
283 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00668
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2007 DAVE MANN FIRE REVIEW Approved
02/20/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1.Provide missing reference data.
2. Show that the hood has 18" clearance to combustible construction or approved methods of clearance reduction.
3. Provide the occupancy of the floor above the kitchen and determine the requirement for fire dampers or a fire-rated shaft for the makeup air ducts and the exhaust duct.
4. Indicate how the make-up air is to be diffused at the supply plenum.
02/20/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
02/20/2007 ROBERT SHERRY WATER REVIEW Approved
02/20/2007 SUZANNE BOHNET ENGINEERING REVIEW Approved
02/21/2007 FSANCHE1 BUILDING-COMMERCIAL REVIEW Needs Review
02/21/2007 FSANCHE1 WWM REVIEW Needs Review
02/21/2007 FSANCHE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
02/21/2007 TERRY STEVENS ZONING REVIEW Approved
02/21/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review