Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM00660
Parcel: 116300170

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM00660
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2007 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied April 25, 2007 CITY OF TUCSON - SECOND CHECK
Tucson Appl. No. T06CM00660
Bureau Veritas Job No. 01007-161001.018

Mr. Todd Rutledge
U.S. Builders
2425 E. Camelback Rd. Ste # 950
Phoenix, Arizona 85016


Re: Plan Review: U.S. Builders-Lot 17 Starr Pass
Address: 2065 S. Twinkling Starr Dr


Dear Mr. Rutledge,

Bureau Veritas North America has completed a second review of the following documents on behalf of the City of Tucson:

Plans: Two (2) sets of building plans (19 sheets, G1.1 through E1.1) dated February 9, 2007 by Soumya Biswas for Consulting Engineers Corporation.

Structural Calculations: Two sets of calculations dated February 9, 2007, by Soumya Biswas for Consulting Engineers Corporation.

Truss Calculations: None submitted with this review.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

Bureau Veritas North America



Shelley Knuffke
ICC Plans Examiner










Re: Stories: One
Occupancy: R-3/VB
Building Area (sq. ft.): 3391 (livable)
973 (porch)
920 (garage)
5284 Total sq. ft.

A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Building Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).



PLUMBING COMMENTS:

Provide a detail for island sink venting.

Plumbing plan not provided

Provide a gas isometric with length of line(horizontal and vertical) to each appliance, BTU demand of each appliances, size of each branch, total demand and size of the meter.

Provide a drainage pipe isometric shoeing all drain, waste and vent piping.

Note that drainage piping serving fixtures which have flood level rims located below the elevation of the next upstream manhole cover of the public sewer shall be protected from backflow of sewage by a backwater valve. IRC Sec P3008.

Specify materials for gas pipes.





If you have any questions regarding the above comments, please contact Randy McCoy at (520) 820-1980 between 8:00 A.M. to 5:00 P.M., M-F.
05/01/2007 GERRY KOZIOL WWM REVIEW Approved
05/18/2007 SREEVES1 ZONING REVIEW Needs Review
05/18/2007 SREEVES1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/18/2007 SUE REEVES OUT TO CUSTOMER Completed