Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T07CM00656
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2007 STEVE SHIELDS ZONING REVIEW Denied Include a copy of the most current approved and stamp site plan for this address. The site plan has been denied by zoning due to inconsistencies with the exisitng conditions and the site plan drawing that was submitted. The ste plan must be drawn based on exisitng conditions (all exisitng buildings must be drawn on the plan) including the building areas that are to be demolished. A separate demo permit must be applied for and approval of the demo must be granted prior to approval of the building permit approval.

David Rivera
Zoning review
04/19/2007 SSHIELD1 NPPO REVIEW Passed
04/19/2007 GERRY KOZIOL WWM REVIEW Approved
04/19/2007 LOREN MAKUS ENGINEERING REVIEW Approved
05/18/2007 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity # T07CM00656
Date: 5/21/07

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

I. STRUCTURAL PLAN:
Clarify DBL 2x8 Lintel on floor plan of studio apartment on page 2.

II. ELECTRICAL PLAN:
Revise note on electrical plan for fan boxes (only approved outlet boxes).

III. OUTDOOR LIGHTING CODE:
Provide the allowable lumen calculations and cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

If you have any questions please contact:
Clayton Trevillyan
(520) 837-4913
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2007 DELMA ROBEY OUT TO CUSTOMER Completed
06/21/2007 DELMA ROBEY REJECT SHELF Completed