Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00650
Parcel: 140430130

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM00650
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2007 ROBERT SHERRY WATER REVIEW Approved
04/18/2007 MARTIN BROWN FIRE REVIEW Denied Sht FX101 states an extra hazard group I design area. Indicate where this area is located and what is in this area.

Indicate design density for high piled storage. Include commodity classification, storage height, rack height, and all other relevant details for determining required sprinkler flow.

Sliding gate (sht. Cl101, note 6) needs to maintain 20' unobstructed access. A fire department lock box will be required. Please show location.

Please confirm flow data obtained from Tucson Airport Fire Department and indicate location of hydrants used for flow test.
04/23/2007 GERRY KOZIOL WWM REVIEW Denied needs manhole tap permit.(8th floor review; 5th floor permit
needs WW/IWC review: Tom Tomchak 579-5721
05/23/2007 JASON GREEN ENGINEERING REVIEW Needs Review
06/06/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/06/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
06/06/2007 SUE REEVES REJECT SHELF Completed