Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T07CM00622
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2007 | DAVE MANN | FIRE | REVIEW | Denied | New tower bollards encroach on 20 foot fire lane between buildings 10 and 11. |
| 02/27/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 2. Please eliminate the redundant ground between the meter and the service disconnect. |
| 03/02/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE PROVIDE MONOPOLE DETAILS IN PLAN SET WITH MINIMUM 1/8" FONT. (DRAWINGS B-1 AND F-1) 2) PLEASE PROVIDE DETAILS FOR SCREEN WALLS, OR CITY OF TUCSON APPROVED ACTIVITY # FOR SCREEN WALLS. SCREEN WALL DETAILS MUST INCLUDE COMPLETE STRUCTURAL ANALYSIS FOR STORAGE BUILDING IF ATTACHED. |
| 03/09/2007 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Denied | Demonstrate compliance with Special Exception conditions a, c, d and e on the plans. Revise dimensions as necessary to comply with conditions for case SE-06-56. |
| 03/15/2007 | TERRY STEVENS | ZONING | REVIEW | Denied | 03/15/07 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The Cell Tower site plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Special Exception section and Structural section of DSD. |
| 03/20/2007 | JAY HOGAN | COMMUNICATIONS | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/20/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 04/20/2007 | SUE REEVES | REJECT SHELF | Completed |