Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00613
Parcel: 12711081A

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T07CM00613
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2007 ANY FIRE REVIEW Active
02/14/2007 ANY MECHANICAL-COMMERCIAL REVIEW Active
02/14/2007 ANY ELECTRICAL-COMMERCIAL REVIEW Active
02/14/2007 ANY WATER REVIEW Active
02/14/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
02/14/2007 ANY WWM REVIEW Active
02/14/2007 ANY PLUMBING-COMMERCIAL REVIEW Active
02/14/2007 ANY ENGINEERING REVIEW Active
02/22/2007 HEATHER THRALL ZONING REVIEW Approved
02/27/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review SITE INVESTIGATION FOR RECCOMENDATIONS ON ISSUING OF PERMIT FOR CofO FOLLOW:
1) THREE STRUCTURES ON SITE (MASONRY OFFICE, WOOD/HT SHOP, AND STEEL PARKING CANOPY) MAY BE REVIEWED AS SINGLE VB BUILDING WITH 3 SUITES.
2) AS BUILT FLOOR PLAN MAY BE ACCEPTED FOR ALL THREE STRUCTURES.
3) OWNER NEEDS TO HAVE LICENSED ELECTRICIAN ENSURE EXISTING ELECTRIC IS IN GOOD REPAIR AND LABEL ALL CIRCUITS.
4) ALL PLUMBING FACILITIES, WALKING SURFACES, DOORS, WINDOWS, ETC TO BE IN GOOD REPAIR AND FUNCTIONING PROPERLY.
5) MASONRY SITE WALL ON SOUTH PROPERTY LINE IS SUITABLE AS FIRE BARRIER FOR STEEL CANOPY BUT 5' SETBACKS ON EAST AND WEST WILL HAVE TO COMPLY WITH TABLE 602 OF 2003 IBC.
6) MASONRY CONSTRUCTION ON EAST SIDE OF NORTH BUILDING IS SUITABLE AS FIRE WALL AND MEETS TABLE 602 REQUIREMENTS.
7) 10' SETBACK FROM EAST PROPERTY LINE FOR BUILDING 2 IS SUITABLE FOR NON-RATED CONSTRUCTION PER TABLE 602.