Permit Number: T07CM00558
Parcel: 141015280

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO

Permit Number - T07CM00558
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Minimum size for DC Ground is #8 (CU). Reference NEC 250.166 (B). This could best be resolved by resizing the GROUND between the Inverter and Meter, and between the Meter and the Existing Electrical Service, in which case that conductor would serve as both Grounding Electrode Conductor and Equipment Grounding Conductor.
2. Minimum font size is 1/8". Current submittal is almost illegible.
3. Provide overcurrent protection for the photovoltaic source circuits. Reference NEC 690.9.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/20/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
03/20/2007 SUE REEVES REJECT SHELF Completed