Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Permit Number - T07CM00558
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Minimum size for DC Ground is #8 (CU). Reference NEC 250.166 (B). This could best be resolved by resizing the GROUND between the Inverter and Meter, and between the Meter and the Existing Electrical Service, in which case that conductor would serve as both Grounding Electrode Conductor and Equipment Grounding Conductor. 2. Minimum font size is 1/8". Current submittal is almost illegible. 3. Provide overcurrent protection for the photovoltaic source circuits. Reference NEC 690.9. |