Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00525
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/27/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/08/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide adequate information to show that the proposed exhaust system complies with the requirements of Section 510, IMC 2003. The current submittal does not include any balancing data, calculations to show that the system was designed employing the constant velocity method, or the gauge of the sheet metal duct. 2. Show how the relief for the dust collector is to be terminated and its location. |
| 04/20/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 04/20/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |