Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM00525
Parcel: 129042660

Address:
323 S NORRIS AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00525
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
03/08/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide adequate information to show that the proposed exhaust system complies with the requirements of Section 510, IMC 2003. The current submittal does not include any balancing data, calculations to show that the system was designed employing the constant velocity method, or the gauge of the sheet metal duct.
2. Show how the relief for the dust collector is to be terminated and its location.
04/20/2007 VFLORES1 WWM REVIEW Needs Review
04/20/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review