Permit Number: T07CM00503
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00503
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
02/09/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Justify the HVAC equipment sizing. Reference Sections 803.2.1 and 803.2.1.1, IECC 2003.
2. Show how recirculation of air from the restrooms will be prevented. Reference Section 403.2.1 (3), IMC 2003.
02/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/09/2007 ROBERT SHERRY WATER REVIEW Approved
02/09/2007 JWILLIA5 BUILDING-COMMERCIAL REVIEW Approved
02/09/2007 ANY ENGINEERING REVIEW Approved
02/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A water supply pressure exceeding 80 PSI requires the installation of a pressure reducing valve. (Note that water pressure calculations using Table 6-5 need to be modified when a pessure reducing valve is installed.) Reference Section 608.2, UPC 2003.
2. Provide an upper terminal cleanout for the lavatories. Reference Section 707.4, UPC 2003.
02/09/2007 MARTIN BROWN FIRE REVIEW Approved
02/14/2007 FSANCHE1 WWM REVIEW Needs Review
02/14/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review