Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00503
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 02/09/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Justify the HVAC equipment sizing. Reference Sections 803.2.1 and 803.2.1.1, IECC 2003. 2. Show how recirculation of air from the restrooms will be prevented. Reference Section 403.2.1 (3), IMC 2003. |
| 02/09/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/09/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/09/2007 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/09/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 02/09/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A water supply pressure exceeding 80 PSI requires the installation of a pressure reducing valve. (Note that water pressure calculations using Table 6-5 need to be modified when a pessure reducing valve is installed.) Reference Section 608.2, UPC 2003. 2. Provide an upper terminal cleanout for the lavatories. Reference Section 707.4, UPC 2003. |
| 02/09/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/14/2007 | FSANCHE1 | WWM | REVIEW | Needs Review | |