Permit Number: T07CM00500
Parcel: 12902020B

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM00500
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2007 GERRY KOZIOL WWM REVIEW Denied SFR ADDITION/REMODEL- RECOUNTED ALL WASTEWATER FIXTURES-needs 8th floor credit evaluation
DOES NOT INCLUDE GARAGE/GUESTHOUSE
NEED TO REVIEW EXSISTING LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER SHOWN ON PLAN
03/19/2007 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied March 12, 2007 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T07CM00500
Bureau Veritas Job No. 01007-161001.020

Tracy Barnett
2542 N. Avenida Valiente
Tucson, Arizona 85715


Re: Plan Review: McCarthy Addition/Remodel
Address: 440 S. Country Club Rd


Dear Tracy Barnett,

Bureau Veritas North America has completed a first review of the following documents on behalf of the City of Tucson:

Plans: Two (2) sets of building plans (19 sheets, 1 through S1.2) dated January 30, 2007, by John E. Grenier for Grenier Engineering, Inc.

Structural Calculations: One (1) set of calculations, dated January 30, 2007, by John E. Grenier for Grenier Engineering, Inc.

Geotechnical Report: None submitted with review.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

Bureau Veritas North America



Randy McCoy
ICC Plans Examiner









RM:pc s:\Tucson\01007-161001.020pc1
enclosures


A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Building Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).


FLOOR PLAN COMMENTS:

Show that each water closet is located in a clear space not less than shown in IRC Figure 307.2.

Provide the following note: A separate insulation inspection prior to drywall or an insulation certificate will be required at time of final. IRC Section N1101.3.1.

An attic access opening shall be provided to attic areas that exceed 30 square feet and have a vertical height of 30 inches or greater. The rough-framed opening shall not be less than 22 inches by 30 inches and shall be located in a hallway or other readily accessible location. A 30 inch minimum unobstructed headroom in the attic space shall be provided at some point above the access opening. IRC Section R807.1.

Glass in hazardous areas shall be safety glass. Specify on applicable floor plans and elevations. IRC Section 308.


ELEVATIONS COMMENTS:

The chimney shall extend at least 2 feet higher (minimum 3 feet at roofline) than any portion of the roof within 10 feet. IRC Table R1003.1.

For thin coat stucco systems over foam board, note and specify the ICC Evaluation Report number, system name and manufacturer. Note and specify the vapor barrier used.


BUILDING CROSS SECTION:

Indicate by drawing and/or notes, how insulation meets the requirements of IRC Section N1101.2.


ROOF PLAN COMMENTS:

Provide ICC Evaluation Report number and manufacturer of all concrete or clay-type tile roofing.

Detail, note and size all roof drains/scuppers. IRC Section R903.4.

Provide attic ventilation calculations for all concealed attic spaces; include required and provided net free ventilation area. Also, indicate the type and location of attic ventilation. Provide the following note, if applicable: "Where eave or cornice vents are installed insulation shall not block the free flow of air. A minimum of 1 inch space shall be provided between the insulation and roof sheathing at the location of the vent”. IRC Section R806.


MECHANICAL COMMENTS:

Show evaporative cooler installation methods. IRC Section M1413.

Show condensate line and secondary condensate line. IRC Section M1411.3 and M1411.3.1.


PLUMBING COMMENTS:

Provide a gas isometric with length of line (horizontal and vertical) to each appliance, BTU demand of each appliance, size of each branch, total demand and size of the meter.

Note that drainage piping serving fixtures which have flood level rims located below the elevation of the next upstream manhole cover of the public sewer shall be protected from backflow of sewage by a backwater valve. IRC Section P3008.


If you have any questions regarding the above comments, please contact Randy McCoy at (520) 820-1980 between 8:00 A.M. to 5:00 P.M., M-F.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2007 DELMA ROBEY OUT TO CUSTOMER Completed
03/23/2007 SUE REEVES REJECT SHELF Completed