Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00499
Parcel: 10701040B

Review Status: Active

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T07CM00499
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2007 ANY ZONING REVIEW Active
02/08/2007 ANY LANDFILL REVIEW Active
02/08/2007 ANY BUILDING-COMMERCIAL REVIEW Active
02/08/2007 ANY ENGINEERING REVIEW Active
02/09/2007 MARTIN BROWN FIRE REVIEW Approv-Cond Sprinkler hazard designation on sht. P1.1 is incorrectly noted as Light Hazard. Fire sprinkler system shall be designed to criteria established in NFPA 13 for a MINIMUM of Ordinary Hazard, Group II.