Permit Review Detail
Review Status: Active
Review Details: PLANS OK TO SUBMIT - 3RD PARTY
Permit Number - T07CM00499
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2007 | ANY | ZONING | REVIEW | Active | |
| 02/08/2007 | ANY | LANDFILL | REVIEW | Active | |
| 02/08/2007 | ANY | BUILDING-COMMERCIAL | REVIEW | Active | |
| 02/08/2007 | ANY | ENGINEERING | REVIEW | Active | |
| 02/09/2007 | MARTIN BROWN | FIRE | REVIEW | Approv-Cond | Sprinkler hazard designation on sht. P1.1 is incorrectly noted as Light Hazard. Fire sprinkler system shall be designed to criteria established in NFPA 13 for a MINIMUM of Ordinary Hazard, Group II. |