Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00485
Parcel: 12902091E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM00485
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2007 SSHIELD1 BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE WEIGHT OF AIR HANDLERS AND JUSTIFY LOAD ON 25 GAUGE STEEL STUDS.

LEERAY HANLY
STRUCTURAL PLANS EXAMINER
909-5154
02/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Modify the trap arm lengths for the lavatories to conform to Table 10-1, UPC 2003. Reference Section 1002.2, UPC 2003.
02/21/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/21/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the condensate drains terminate in an area capable of absorbing the water with no surface runoff.
2. Provide maintenance access to the air handlers.
02/28/2007 FSANCHE1 WWM REVIEW Needs Review
02/28/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/28/2007 FSANCHE1 OUT TO CUSTOMER Completed