Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM00485
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/21/2007 | SSHIELD1 | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE WEIGHT OF AIR HANDLERS AND JUSTIFY LOAD ON 25 GAUGE STEEL STUDS. LEERAY HANLY STRUCTURAL PLANS EXAMINER 909-5154 |
02/21/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Modify the trap arm lengths for the lavatories to conform to Table 10-1, UPC 2003. Reference Section 1002.2, UPC 2003. |
02/21/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/21/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the condensate drains terminate in an area capable of absorbing the water with no surface runoff. 2. Provide maintenance access to the air handlers. |
02/28/2007 | FSANCHE1 | WWM | REVIEW | Needs Review | |
02/28/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/28/2007 | FSANCHE1 | OUT TO CUSTOMER | Completed |