Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2007 HEATHER THRALL ZONING REVIEW Approved
02/08/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Show the size, routing, and termination of the condensate drains. Reference Section 307.2, IMC 2003 and Section 807.2, UPC 2003.
3. Provide details to show how the air handlers are suspended from the building structure. Reference Section 302.1, IMC 2003.
4. Provide auxiliary drain pans or secondary drain systems for air handling units. Reference Section 307.2.3 IMC 2003.
5. Show how the specified heat pumps are capable of maintaining a minimum temperature of 68°F in the interior spaces intended for occupancy on a design heating day (32°F). Reference Sections 309.1 and 312.1, IMC 2003.
02/08/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00485 2/8/07

1. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
2. Provide overcurrent protection for the new feeder.
3. Indicate the location of the new service on the plans.
4. Provide catalogue cut sheets for new exterior fixtures.
5. Provide available fault current.
6. Provide fault calculations.
7. This building would already have an electrical service. Justify the installation of a new electrical service. Reference NEC 230.2. note other requirements if this is the case, for example 230.2 (E) and Bonding per NEC 250.
7. Provide a Service Disconnect per NEC 230 Part VI.
8. Size the Grounding Electrode Conductor. Reference NEC 250.66.
02/08/2007 ROBERT SHERRY WATER REVIEW Approved
02/08/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY TOTAL SQ. FOOTAGE OF THIS SUITE.
2) PROVIDE DRINKING FOUNTAIN PER TABLE 2902.1
3) CLARIFY THAT EXISTING ROOF FRAMING CAN CARRY NEW LOADS FROM NEW MECHANICAL UNITS.
4) CLARIFY EXISTING OCCUPANTS ON SITE PLAN TO JUSTIFY MOST RESTRICTIVE USE.
5) ELIMINATE SUITE NUMBER 103 OFF OF TITLE BLOCK.
02/08/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/08/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
2. The trap and trap arm for a lavatory may not be increased more than one size larger than the minimum trap size shown in Table 7-3. Reference Section 1003.3, UPC 2003.
3. Coordinate the plumbing plan and the waste & vent riser diagram. Reference Section 103.2.3, UPC 2003.
4. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for business occupancy.
02/08/2007 MARTIN BROWN FIRE REVIEW Approved
02/20/2007 DROBEY1 WWM REVIEW Needs Review
02/20/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review