Permit Number: T07CM00479
Parcel: 13355230A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00479
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2007 MARTIN BROWN FIRE REVIEW Approved
02/08/2007 SUZANNE BOHNET ENGINEERING REVIEW Approved
02/08/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00479 2/8/07

1. Water Heater specified appears to run on 240V power. Electrical provides 208V. Coordinate with Plumbing and clarify.
2. Two sets required for over-the-counter service.
02/13/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide balancing data for the HVAC system.
2. Revise the ventilation calculations per Section 403, IMC 2003.
4. Revise the dryer vent design to comply with the manufacturer's recomendations.
02/13/2007 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
02/13/2007 ROBERT SHERRY WATER REVIEW Approved
02/13/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water is to be controlled to the lavatory. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
2. Provide shower and tub/shower control valves that comply with the requirements of Section 420.0, UPC 2003.
3. Provide a waste and vent riser diagram.
02/13/2007 DROBEY1 WWM REVIEW Needs Review
02/13/2007 DROBEY1 ZONING REVIEW Needs Review
02/13/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2007 DELMA ROBEY APPROVAL SHELF Completed
02/13/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/13/2007 DELMA ROBEY REJECT SHELF Completed