Permit Number: T07CM00439
Parcel: 12403207B

Address:
1628 E 6TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM00439
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/13/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section 801.3, UPC 2003 allows a bar sink to be indirectly wasted if the trap for the sink cannot be vented. It does not appear that the sink is located in such a position.
2. The cut sheet for the ice machine did not clarify the presence or absence of an approved backflow device or an air gap. Provide design guidance for the contractor; Arizona State law does not allow the contractor to provide designs. (Note that the cut sheet for the ice machine indicates that two independent indirect waste lines will be required for the condensate and the bin drain.)
02/13/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/16/2007 GERRY KOZIOL WWM REVIEW Approved