Permit Number: T07CM00439
Parcel: 12403207B

Address:
1628 E 6TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00439
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
02/06/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size of the combustion air duct for the mechanical room. Is this a one-opening system?
02/06/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00439 2/6/07

1. Please identify an electrical panel and circuit for the Exhaust Fan indicated on Sheet M-1.
02/06/2007 ROBERT SHERRY WATER REVIEW Approved
02/06/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
02/06/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/06/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Where is the water heater?
2. Show the gas piping to the furnace and the water heater.
3. Show the automatic shut off valve for the equipment under the hood.
4. Show the applicable standards for the owner-furnished fixtures.
5. Justify indirectly wasting the new bar sink (keynote 9).
6. If the ice machine does not have an approved air gap or integral backflow protection assembly, provide an approved backflow protection device.
02/06/2007 DAVE MANN FIRE REVIEW Approved
02/13/2007 DROBEY1 WWM REVIEW Needs Review
02/13/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2007 DELMA ROBEY APPROVAL SHELF Completed
02/13/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/13/2007 DELMA ROBEY REJECT SHELF Completed