Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T07CM00417
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/30/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00417 7/30/07 1. Account for both Sewage Pumps on the panel schedule and load calculations. 2. Account for additional lighting fixture on panel schedule and load calculations. |