Permit Number: T07CM00417
Parcel: 12308007C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00417
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
02/05/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/05/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/05/2007 ROBERT SHERRY WATER REVIEW Approved
02/05/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE DETAILS FOR FRAMING.

2) DETAIL ANSI 117.1 PROVISIONS FOR LOCATION OF CONTROLS, GRAB BARS, TRANSFER SEAT AND THRESHOLD.
02/05/2007 LOREN MAKUS ENGINEERING REVIEW Approved
02/05/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Show that the use of gravity drainage from the new sower and lavatory is not practicable. Reference Section 709.0, UPC 2003.
3. If gravity drainage is not practicable, revise the sump pump system to comply with the requirements of Section 710.0, UPC 2003 for public installations (e.g. 3" minimum drainage line, duplex pumps, audible and visual alarms).
4. Provide a cleanout for the horizontal drainage line from the sump pump. Reference Section 707.12, UPC 2003.
02/05/2007 DAVE MANN FIRE REVIEW Approved
02/09/2007 DROBEY1 WWM REVIEW Needs Review
02/09/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2007 DELMA ROBEY APPROVAL SHELF Completed
02/09/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/09/2007 DELMA ROBEY REJECT SHELF Completed