Permit Number: T07CM00400
Parcel: 13322471B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00400
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2007 DAVE MANN FIRE REVIEW Approved
02/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that there is adequate ventilation for the restrooms. Reference Section 403.3, IMC 2003.
02/02/2007 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
02/02/2007 ROBERT SHERRY WATER REVIEW Approved
02/02/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved 1) CLARIFY ADDRESS AND ALL SUITES ON SITE PLAN. RECORDS SHOW SUITE 170 WITH EXISTING M OCC OF 8600 SQ FEET.

2) JUSTIFY NON SEPARATED USE. CORRECT GENERAL BUILDING SUMMARY ALLOWABLE AREA FIGURES. JUSTIFY AREA INCREASE ALLOWANCES.
02/02/2007 ANY ENGINEERING REVIEW Approved
02/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Complete the water isometric. Reference Section 103.2.3, UPC 2003.
3. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for mercantile occupancy.
4. Provide fixture descriptions for all plumbing fixtures. Reference Section 401.1, UPC 2003.
5. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
6. Provide equipment data for the water heater. Reference Section 103.2.3, UPC 2003.
7. Provide a detail of the water heater installation, including if appropriate, the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003.
8. Coordinate the plumbing schedule, plans, and riser diagrams. Reference Section 103.2.3, UPC 2003.
9. Show the plumbing fixtures and drainage fittings installed correctly and in a manner consistent with the Code and the manufacturer's instructions. Reference Sections 304.0 and 310.4, UPC 2003.
02/06/2007 HEATHER THRALL ZONING REVIEW Approved
02/16/2007 VFLORES1 WWM REVIEW Needs Review
02/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review