Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00375
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/16/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
02/16/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
02/16/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
02/16/2007 | ROBERT SHERRY | WATER | REVIEW | Passed | |
02/16/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/19/2007 | GERRY KOZIOL | WWM | REVIEW | Passed | |
03/19/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Denied 2/21/07 by Ray Mahuta. Comments on Application. T07CM00375 2/26/07 1. 2 sets of 350 MCM is not a reasonable conduit size for a 1200A service. Please reconsider fault calculations. 2. Panels GA is not accounted for in service load calculations, but they are shown on the line diagram. 3. Fill in electrical load for Panels HP, B2, A1, and A2 on service load cauluclations. |
03/19/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |