Permit Number: T07CM00375
Parcel: 124041020

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00375
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
02/16/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/16/2007 ROBERT SHERRY WATER REVIEW Passed
02/16/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
03/19/2007 GERRY KOZIOL WWM REVIEW Passed
03/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved Denied 2/21/07 by Ray Mahuta. Comments on Application.

T07CM00375 2/26/07

1. 2 sets of 350 MCM is not a reasonable conduit size for a 1200A service. Please reconsider fault calculations.
2. Panels GA is not accounted for in service load calculations, but they are shown on the line diagram.
3. Fill in electrical load for Panels HP, B2, A1, and A2 on service load cauluclations.
03/19/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed