Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T07CM00375
Parcel: 124041020

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00375
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE DETAILS FOR DEMISING WALLS.

2) PROVIDE DETAILS FOR ACCESSIBLE RAMP INCLUDING HAND RAIL DESIGN.
02/01/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the roof structure can support the rooftop units and details to show how the rooftop units are mounted on the roof.
2.. Show the size, route, and termination of the condensate drains for the rooftop units.
02/01/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00375 2/1/07

1. It appears that the volt-ampere count on the panel schedule is low for the HPs.
2. Account for the largest motor on the panel schedule.
3. Provide conduit and conductor size and type for motor feeders.
4. Provide maintenance receptacles for HPs. Reference NEC 210.63.
5. Show the location of the disconnect switch on the plans.
6. Provide TEP Available Fault current.
7. Provide fault calculations.
8. Provide service load calculations.
02/01/2007 ROBERT SHERRY WATER REVIEW Passed No water service shown
02/01/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the termination points of the two building drains and the grease waste.
2. Provide a design for the gas piping for the two rooftop units.
02/01/2007 SUZANNE BOHNET ENGINEERING REVIEW Approved
02/14/2007 DAVE MANN FIRE REVIEW Approved
02/16/2007 CAGUILA1 WWM REVIEW Needs Review
02/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/16/2007 CAGUILA1 ZONING REVIEW Needs Review