Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00375
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/01/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE DETAILS FOR DEMISING WALLS. 2) PROVIDE DETAILS FOR ACCESSIBLE RAMP INCLUDING HAND RAIL DESIGN. |
02/01/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the roof structure can support the rooftop units and details to show how the rooftop units are mounted on the roof. 2.. Show the size, route, and termination of the condensate drains for the rooftop units. |
02/01/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00375 2/1/07 1. It appears that the volt-ampere count on the panel schedule is low for the HPs. 2. Account for the largest motor on the panel schedule. 3. Provide conduit and conductor size and type for motor feeders. 4. Provide maintenance receptacles for HPs. Reference NEC 210.63. 5. Show the location of the disconnect switch on the plans. 6. Provide TEP Available Fault current. 7. Provide fault calculations. 8. Provide service load calculations. |
02/01/2007 | ROBERT SHERRY | WATER | REVIEW | Passed | No water service shown |
02/01/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the termination points of the two building drains and the grease waste. 2. Provide a design for the gas piping for the two rooftop units. |
02/01/2007 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
02/14/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
02/16/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
02/16/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
02/16/2007 | CAGUILA1 | ZONING | REVIEW | Needs Review |