Permit Number: T07CM00364
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00364
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
01/31/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
01/31/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review ok to submit 2/5/7
01/31/2007 ROBERT SHERRY WATER REVIEW Approved
01/31/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
01/31/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide an upper terminal cleanout for the new sink. Reference Section 707.4, UPC 2003 as amended by the City of Tucson.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
01/31/2007 MARTIN BROWN FIRE REVIEW Approved
02/05/2007 DROBEY1 WWM REVIEW Needs Review
02/05/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/05/2007 DROBEY1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/05/2007 DELMA ROBEY APPROVAL SHELF Completed
02/05/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/05/2007 DELMA ROBEY REJECT SHELF Completed