Permit Number: T07CM00352
Parcel: 130054590

Address:
2114 S MCFEE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM00352
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2007 SREEVES1 2ND PARTY REVIEW REVIEW Denied March 28, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Heiderman Residence Addition – 2nd REVIEW
CITY OF TUCSON LOG NO. T07CM00352
WILLDAN PROJECT NO. 13881-7031

The second review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
R-3 N/A V-B 1,102 No Smoke

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
Reviewed and accepted.

ARCHITECTURAL COMMENTS:
Sheet A5.1
Show calculation of attic ventilation area. Note location of all vents needed to comply or show compliance with an accepted Non-vented Roof Method Details 1-8, dated 7/18-19/2001 as permitted by Section R104.11, Alternate Methods. Reference IRC Section R806.2. Comment remains. Not Addressed.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Reviewed and accepted.

MECHANICAL COMMENTS:
Sheet A6.1
Show on the plans how mechanical fresh air will be provided if using one of the non-vented roof methods. Reference Non-Vented Roof Details dated 7/18-19/2001. Comment remains. Not Addressed.


ELECTRICAL COMMENTS:
Sheet A6.1
Please provide cut sheets for all the exterior light fixtures shown. The cut sheets need to provide lumens per fixture and show if the fixture is a full cut-off, which means no light is emitted at or above the horizontal plane. Reference the City of Tucson Outdoor Lighting Code. Comment remains. Not Addressed.

Cross-reference exterior lighting fixtures on the plans with the cut sheets and calculations submitted. Reference the City of Tucson Submittal Requirements. Comment remains. Not Addressed.

ENERGY CODE COMMENTS:
Sheet A1.2
Please submit the required energy code calculations by using the “RES” check program, Chapter 11 of the IRC, or the 2003 IECC, and also annotate on the plans. Reference IRC Section R106.1.1. Comment remains. Not Addressed.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.



Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb

Final Status

Task End Date Reviewer's Name Type of Review Description
04/03/2007 DELMA ROBEY OUT TO CUSTOMER Completed
03/29/2007 SUE REEVES REJECT SHELF Completed