Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM00332
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/16/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 04/23/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CODE ANALYSIS SHOULD REFLECT ENTIRE STORAGE BUILDING AREA UNLESS A FIRE WALL IS BUILT BETWEEN THE EXISTING AND NEW. 1159 SQ. FT. (EXISTING + NEW) FOR VB CONSTRUCTION IS OK. 2) E-1 SHEARWALL IS NOTED AT USING OSB IN ENGINEERS CALCS BUT IS GYP ON PLANS. PLEASE CORRECT. 3) E-2 SHEARWALL REQUIRES SIMPSON PHD2-SD53 HOLDDOWN PER ENGINEERS CALCS. PLEASE DETAIL ON PLAN. 4) ELEVATIONS CALL FOR 2X6 FASCIA AND RIM JOIST; DETAILS CALL FOR 2X7, PLEASE HAVE INFORMATION MATCH. 5) IS IT YOUR INTENTION THAT CONTRACTOR USE 3/4" PLYWOOD FOR DECKING? 1/2" SHEATHING WOULD BE ACCEPTABLE AND IS NORMAL CONSTRUCTION PRACTICE. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/01/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 05/01/2007 | SUE REEVES | REJECT SHELF | Completed |