Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2007 DAVE MANN FIRE REVIEW Approved
04/23/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) CODE ANALYSIS SHOULD REFLECT ENTIRE STORAGE BUILDING AREA UNLESS A FIRE WALL IS BUILT BETWEEN THE EXISTING AND NEW. 1159 SQ. FT. (EXISTING + NEW) FOR VB CONSTRUCTION IS OK.

2) E-1 SHEARWALL IS NOTED AT USING OSB IN ENGINEERS CALCS BUT IS GYP ON PLANS. PLEASE CORRECT.

3) E-2 SHEARWALL REQUIRES SIMPSON PHD2-SD53 HOLDDOWN PER ENGINEERS CALCS. PLEASE DETAIL ON PLAN.

4) ELEVATIONS CALL FOR 2X6 FASCIA AND RIM JOIST; DETAILS CALL FOR 2X7, PLEASE HAVE INFORMATION MATCH.

5) IS IT YOUR INTENTION THAT CONTRACTOR USE 3/4" PLYWOOD FOR DECKING? 1/2" SHEATHING WOULD BE ACCEPTABLE AND IS NORMAL CONSTRUCTION PRACTICE.