Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the minimum font size to 1/8", all upper case.
2. Revise the screened background on the drawing to be legible.
3. Provide an electrical plan for the installation of the pump and boiler.
4.Show that the installation of the boiler provides adequate clearances from the enclosing room walls and maintenence access. Arizona State boiler inspection required.
5. Provide details to show the actual locations of the pump air separator and how they are to be supported from the structure.
6. Indicate the construction of the walls of the boiler room.
01/30/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the minimum font size to 1/8", all upper case.
2. Revise the screened background on the drawing to be legible.
3. Show that the net free area of the combustion and relief openings conforms to the requirements of Section 507, UPC 2003.
4. Revise the size of the natural gas piping to the boiler per Table 12-7, UPC 2003.