Permit Number: T07CM00320
Parcel: 135022440

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM00320
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2007 GERRY KOZIOL WWM REVIEW Approved
03/05/2007 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied February 28, 2007 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T07CM00320
Bureau Veritas Job No. 01007-161001.014

Maritza Dicenso
7810 E. Hawthorne
Tucson, Arizona 85710


Re: Plan Review: Park Addition
Address: 6409 Calle Castor


Dear Maritza Dicenso,

Bureau Veritas North America has completed a first review of the following documents on behalf of the City of Tucson:

Plans: Two (2) sets of building plans (8 sheets, 1 through 8) no dates, no stamps.

Structural Calculations: None submitted with review.

Geotechnical Report: None submitted with review.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

Bureau Veritas North America



Randy McCoy
ICC Plans Examiner









RM:pc s:\Tucson\1007-161001.014pc1
enclosures

Re: Stories: One
Occupancy/Const.: R-3/VB
Building Area (sq. ft.): 546 (Livable)
175 (Porch)
721 Total sq. ft.

A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Building Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).


ELEVATION COMMENTS:

Indicate all materials used - stucco, concrete block, glass block, roofing systems, siding, veneers, etc. IRC Section R703.

For thin coat stucco systems over foam board, note and specify the ICC Evaluation Report number, system name and manufacturer. Note and specify the vapor barrier used.


BUILDING CROSS SECTION:

Indicate by drawing and/or notes, how insulation meets the requirements of IRC Section N1101.2.


ROOF PLAN COMMENTS:

Note and specify a complete roofing system: specify roofing type, grade of materials, valley flashing material, underlayment required and method of installation, attachments of roofing materials as required by IRC Chapter 9.

Note and specify all roof slopes. IRC Chapter 9.

Provide attic ventilation calculations for all concealed attic spaces; include required and provided net free ventilation area. Also, indicate the type and location of attic ventilation. Provide the following note, if applicable: "Where eave or cornice vents are installed insulation shall not block the free flow of air. A minimum of 1 inch space shall be provided between the insulation and roof sheathing at the location of the vent”. IRC Section R806.


FRAMING PLAN COMMENTS:

Show layout and identify structural support system including girders, joists, rafters, posts, beams, blocking and decking.

Indicate all braced wall panel locations. Specify the method of bracing to be used. A sealed lateral analysis, prepared by an Arizona Registrant, will be required if the bracing does not comply with the conventional provisions. IRC Section R602.

Specify lumber grade, species and size of members. IRC Section R602.

Provide complete floor (if applicable) and roof framing plans. Specify size and spacing of all framing members. Indicate all post sizes. IRC Section R106.

Show required holddowns, as specified on lateral design or as required for all alternate braced wall panels, on the foundation plan.

Detail and specify anchorage for trusses.

TRUSS SYSTEMS: Trusses can be submitted as a “Deferred Submittal” for custom homes only. However, they must be submitted and approved prior to their fabrication.

Provide complete truss calculations and truss layout plan. Truss designs submitted must include all types and be designed for the loading conditions, span, slope, and spacing designated on the framing plan.

Truss calculations must be signed, dated and sealed by an Engineer who is registered in the State of Arizona.

The seal on the truss calculations shall be dated within the latest adopted IRC.

All truss calculations shall be cross-referenced to the truss layout or the roof and floor framing plans.

Specify all hangers used to hang trusses from girder trusses, walls, or other locations. IRC Section R802 & ANSI-TPI 1995.


MECHANICAL COMMENTS:

Show condensate line and secondary condensate line. IRC Section M1411.3 and M1411.3.1.


PLUMBING COMMENTS:

Specify materials for waste, water and gas pipes.

ELECTRICAL COMMENTS:

Provide a complete electrical plan. Indicate the location of all air conditioning and heating units, air handlers, compressors and disconnects. IRC Section R106.1.


If you have any questions regarding the above comments, please contact Randy McCoy at (520) 820-1980 between 8:00 A.M. to 5:00 P.M., M-F.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/14/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/14/2007 SUE REEVES REJECT SHELF Completed