Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T07CM00307
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2007 | GERRY KOZIOL | WWM | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/28/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 08/28/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/28/2007 | DELMA ROBEY | REJECT SHELF | Completed |