Permit Number: T07CM00307
Parcel: 121092290

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM00307
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

As of 6/12/2007 the City of Tucson has adopted the 2006 IRC with the exception of the plumbing portion which has been replaced with the 2006 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

SITE PLAN:

1. Show the water pipe size from the meter to the building. Show the point of connection for the proposed hot and cold branches. The pipe must be sized for the calculated load, 2006 UPC 610.1.

STRUCTURAL PLANS:

1. Show the size of all framing members (headers over door opening #5, 6 and hallway), Table 502.5(1) & (2).
2. Note that scissor truss installation may require using (TC) slotted ties with appropriate uplift rating at one wall connection, R802.10.5.
3. Specify and detail all over-framing connections for intersecting pitched roof assemblies.

SECTIONS - DETAILS:

1. Specify water-resistive barrier over wall framing or sheathing, R703.6.3.
2. Show insulation applied to the roof deck side of unvented conditioned attic spaces with no vapor retarders at the ceiling, R806.4.

PLUMBING PLANS:

1. The City of Tucson has adopted the 2006 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code, or appeal to the Building Official for IRC design approval.
2. Provide water pressure range and the maximum developed length of water line and diameter from the meter (may require upgrading existing), UPC 610.8, Table 6-6.

ELECTRICAL PLANS:

1. Bathroom receptacles shall be on a separate 20 AMP circuit with no other outlets, E3603.4.
2. Hallways of 10' or more in length require a receptacle (show if existing), E3801.10.
3. Indicate the location of all disconnect switches for air handling equipment, E4001.5.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.
2. Provide cut sheets for all full cut-off fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review