| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2007 | DAVE MANN | FIRE | REVIEW | Denied | Provide fire wall at east property line of sign application carport. |
| 01/26/2007 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Clarify there is a cross access agreement for accessibility from handicap parking to the building since properties are owned by separate people. 2) It appears via research in records that the attached existing carport has not been permitted. Please provide justification that it was permitted or provide structrual calculations and permit drawings. 3) Clarify fire resistance rating of carport structure per table 602 based on distance from property line. |
| 02/02/2007 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/12/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information to show that the offices, restrooms, and the sign shop meet the ventilation requirements of Section 403, IMC 2003. |
| 02/12/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the site drawing to show the location of the natural gas meter. Reference Section 103.2.3, UPC 2003. 2. Revise the site drawing to show the location of the sewer connection. Reference Section 103.2.3, UPC 2003. |
| 02/12/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | Revise the site drawing to show the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 2003. |
| 02/13/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/20/2007 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Kayo Signs T07CM00295 Building Plan (1st Review) TRANSMITTAL DATE: February 20, 2007 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180. C:\planning\grading\t07cm00295.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 02/21/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | An approved site plan is required prior to building plan approval. |
| 02/22/2007 | GERRY KOZIOL | WWM | REVIEW | Passed |