Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00267
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/23/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 01/23/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/23/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/23/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/23/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the waste and vent isometric to coordinate with the plumbing plan. 2. A 2" vent is required for water closets. Reference footnote 3, Table 7-5, UPC 2003. 3. Show how the new waste piping relates to the existing piping. 4. Provide cleanouts sized per Section 707.11 (Table 7-6), UPC 2003. |
| 01/23/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 04/03/2007 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | 1) 2ND EXIT DOES NOT MEET 1/2 DIAGONAL SEPERATION DISTANCE PER 10.14.2.1 OF 2003 IBC 2) CLARIFY ACCESSIBILITY AT RESTROOMS PER ANSI 117.1 FIGURES 404.2.3.1. PLEASE CLARIFY HARDWARE. 3) CLARIFY HOW 1 HOUR CORRIDOR REQUIREMENTS HAVE BEEN MET. PROVIDE DETAILS FOR WALL FRAMING AND FIRE STOP SYSTEMS. C/A2 DOES NOT ADDRESS THIS. 4) CLARIFY HOW BEER CAVE ENTRANCE MEETS ANSI 117.1 SECTION 404.2.1. |
| 04/03/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 04/03/2007 | GBONILL1 | FIRE | REVIEW | Needs Review | |
| 04/03/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |