Permit Number: T07CM00267
Parcel: 12403205A

Address:
1610 E 6TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00267
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2007 TERRY STEVENS ZONING REVIEW Approved
01/23/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/23/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/23/2007 ROBERT SHERRY WATER REVIEW Approved
01/23/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the waste and vent isometric to coordinate with the plumbing plan.
2. A 2" vent is required for water closets. Reference footnote 3, Table 7-5, UPC 2003.
3. Show how the new waste piping relates to the existing piping.
4. Provide cleanouts sized per Section 707.11 (Table 7-6), UPC 2003.
01/23/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/03/2007 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review 1) 2ND EXIT DOES NOT MEET 1/2 DIAGONAL SEPERATION DISTANCE PER 10.14.2.1 OF 2003 IBC

2) CLARIFY ACCESSIBILITY AT RESTROOMS PER ANSI 117.1 FIGURES 404.2.3.1. PLEASE CLARIFY HARDWARE.

3) CLARIFY HOW 1 HOUR CORRIDOR REQUIREMENTS HAVE BEEN MET. PROVIDE DETAILS FOR WALL FRAMING AND FIRE STOP SYSTEMS. C/A2 DOES NOT ADDRESS THIS.

4) CLARIFY HOW BEER CAVE ENTRANCE MEETS ANSI 117.1 SECTION 404.2.1.
04/03/2007 GBONILL1 WWM REVIEW Needs Review
04/03/2007 GBONILL1 FIRE REVIEW Needs Review
04/03/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review