Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00253
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 01/22/2007 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 01/23/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/23/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The minimum font size for all drawings is 1/8", all upper case. 2. Indicate any changes to the ductwork or air device locations. |
| 01/23/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/23/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/23/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a complete plumbing plan, including waste and vent and water riser diagrams. 2. Specify the required backflow assemblies to be used with directly connected appliances. 3. The minimum font size for all drawings is 1/8", all upper case. |
| 02/15/2007 | FSANCHE1 | WWM | REVIEW | Needs Review | |
| 02/15/2007 | FSANCHE1 | FIRE | REVIEW | Needs Review | |
| 02/15/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/15/2007 | FSANCHE1 | OUT TO CUSTOMER | Completed |