Permit Number: T07CM00249
Parcel: 127130240

Address:
5830 E BURNS ST

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM00249
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Minimum size for DC Ground is #8 (CU). Reference NEC 250.166 (B). This could best be resolved by resizing the GROUND between the Inverter and Meter, and between the Meter and the Existing Electrical Service, in which case that conductor would serve as both Grounding Electrode Conductor and Equipment Grounding Conductor.
2. Add the following labeling to the 20/2 breaker at the Existing Service: "Photovoltaic disconnect located on east exterior wall."
3. Add the following labeling to the Inverter (Photovoltaic Disconnect): "Utility disconnect located on south exterior wall."
4. Minimum font size is 1/8". Please blow up lettering as much as practicable, as we reduce by 50% for the purpose of archiving.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/20/2007 GERARDO BONILLA REJECT SHELF Completed