02/27/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied February 26, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Maldonado Garage/Patio Addition
CITY OF TUCSON LOG NO. T07CM00241
WILLDAN PROJECT NO. 13881-7014 – 1ST REVIEW

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
Garage
Porch N/A V-B 2094
2080 No None

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
Trusses

GENERAL COMMENTS:
General
A deferred submittal letter for trusses will need to be forwarded directly to the Building Official and approved prior to the plans being delivered to the City. Reference the City of Tucson Submittal Policy.

All Sheets
All lettering should be a minimum of 1/8” high capitalized. Please comply. Reference the City of Tucson Submittal Requirements.

ARCHITECTURAL COMMENTS:
Sheets 2 and 3
All exterior doors require a landing or floor at the exterior. Landings must be at least as wide as the doors they serve and 36” in the direction of travel. Reference IRC Section R311.4.3.


Sheet 3
Provide ½” gypsum board on all walls common to the garage and house in compliance with R309.2. Where separation is a floor-ceiling assembly, the structure supporting the separation shall also be protected by a minimum ½” gypsum board or equivalent. Reference IRC Section R309.2.

Openings between the garage and residence shall be equipped with solid wood doors not less than 1 3/8” (35mm) thick, solid or honeycomb core steel doors not less than 1 3/8” (35mm) thick, or 20-minute fire rated doors. Reference IRC Section 309.1.

Sheet 5
Note and specify all roof slopes appropriate to material, (minimum allowable roof slope is ¼” per foot). Reference IRC Section R905.

Show calculation of attic ventilation area. Note location of all vents needed to comply or show compliance with an accepted Non-vented Roof Method Details 1-8, dated 7/18-19/2001 as permitted by Section R104.11, Alternate Methods. Reference IRC Section R806.2.

Cross-sections shall be cross-referenced to the floor plan and framing plans. Reference IRC Section R106.1.1.

STRUCTURAL COMMENTS:
Sheet 2
Indicate the slope for exterior slabs. Reference IRC Section R311.6.1.

Specify design criteria on plans. Provide values for floor dead load and live load, as well as roof dead load and live load. Reference IRC Sections R301.4 and R301.5.

Sheet 5
Detail # 1 shows finished grade at being on the outside part of the garage, when this side is where the existing residence should be. Please clarify and correct. Reference 2003 IRC Section 106.1.1.

PLUMBING COMMENTS:
Not part of this review.

MECHANICAL COMMENTS:
Not part of this review.

ELECTRICAL COMMENTS:
Sheet 3
Note on plans: “All electrical work shall comply with 2003 IRC Chapters 33-42.” Reference IRC Section E3301.2 and the City of Tucson Submittal Requirements.

Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used. Reference IRC Section E4001.6.

Electrical load calculations are required when more than 4 circuits are added. Reference IRC Section 106.1.1 and the City of Tucson Submittal Requirements.

Submit panel schedule showing wire size. Reference IRC Section 3502.2 and the City of Tucson Submittal Requirements.

Please provide cut sheets for all the exterior light fixtures shown or noted. The cut sheets need to provide lumens per fixture and show if the fixture is a full cut-off, which means no light is emitted at or above the horizontal plane. Please provide cut sheets and calculations for all exterior lighting fixtures. Reference the City of Tucson Outdoor Lighting Code.

Please specify how many lamps of each type are being used for the exterior lighting. Lumens will be calculated by the maximum allowed watts for each fixture that the manufacturer specifies. Reference the City of Tucson Outdoor Lighting Code.

Cross-reference exterior lighting fixtures on the plans with the cut sheets and calculations submitted. Reference the City of Tucson Submittal Requirements.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb