04/09/2008 JIMHOFF1 ZONING-CITY HALL REVIEW Denied T07CM00238 – Plan Review Comments (SE-07-11 Verizon Wireless – 2770 S. Harrison Road, C-2 Zone)

The decision letter for special exception case number SE-07-11 was received and the plans were reviewed for compliance with the conditions as specified in the letter. Please reference the special exception case number (SE-07-11) on the plans.

The plans indicated that the offset (stand off arm) was 22 inches. The condition requires that the offset not exceed 18 inches.

Wire ports are not indicated on the plans. Notes indicating that the cables shall be routed through the interior of the pole and that the cables shall not be visible are to be included on the plans.


A statement certifying that the monopole and cellular communication equipment are in compliance with all zoning and building codes must be included on the plans.

The plans must include the dimensions of monopole diameter at the pole base, top and point of antenna attachment.


The plans must include a note specifying that all new pole-mounted equipment shall be painted to match the existing pole and that the proposed equipment shelter shall be natural earth tones.
04/09/2008 HEATHER THRALL ZONING REVIEW Denied Please see the last review comments for zoning, and resubmit the plans once they are corrected. Resubmit to the permit counter and the plans will be routed to all divisions needing to see the corrections.

Zoning review, even if there are no further zoning comments to address on this next resubmittal, cannot approve the plans until Planning has certified that all conditions of the special exception are met and approved and stamped.

My email is Heather.Thrall@tucsonaz.gov