Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM00238
Parcel: 13613001U

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM00238
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2008 Michael Wyneken ZONING-CITY HALL REVIEW Completed T07CM00238 – Plan Review Comments (SE-07-11 Verizon Wireless – 2770 S. Harrison Road, C-2 Zone)

The decision letter for special exception case number SE-07-11 was received and the plans were reviewed for compliance with the conditions as specified in the letter. Please reference the special exception case number (SE-07-11) on the plans.

The plans indicated that the offset (stand off arm) was 22 inches. The condition requires that the offset not exceed 18 inches.

Wire ports are not indicated on the plans. Notes indicating that the cables shall be routed through the interior of the pole and that the cables shall not be visible are to be included on the plans.


A statement certifying that the monopole and cellular communication equipment are in compliance with all zoning and building codes must be included on the plans.

The plans must include the dimensions of monopole diameter at the pole base, top and point of antenna attachment.


The plans must include a note specifying that all new pole-mounted equipment shall be painted to match the existing pole and that the proposed equipment shelter shall be natural earth tones.