Permit Number: T07CM00235
Parcel: 12901038A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00235
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2007 MARTIN BROWN FIRE REVIEW Approved
01/23/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/23/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00235 1/23/07

1. Provide conductor size for kiln, AC, and Air Compressor.
2. Provide load calculations for panel and service, and rating of service.
3. Clarify panel feeder size. 3/2 what? 1/2 what?
4. Provide fault calculations and fault current rating of panel.
01/23/2007 ROBERT SHERRY WATER REVIEW Approved
01/23/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY SEPERATED/NON-SEPERATED USE.

2) ALLOWABLE AREA FOR BUILDING HAS BEEN BASED ON F2 OCCUPANCY. CLARIFY THAT IS MOST RESTRICTIVE CLASSIFICATION FOR THIS BUILDING IF YOU ARE TRYING TO USE NON-SEPERATED USE PROVISIONS. CLARIFY ADJACENT TENANTS AND RATING OF DEMISING WALLS IF USING SEPERATED USE PROVISIONS.
01/23/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/06/2007 GBONILL1 WWM REVIEW Needs Review
04/06/2007 GBONILL1 ZONING REVIEW Needs Review
04/06/2007 GBONILL1 ENGINEERING REVIEW Needs Review
04/06/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review