Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/22/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/23/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
01/23/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00235 1/23/07 1. Provide conductor size for kiln, AC, and Air Compressor. 2. Provide load calculations for panel and service, and rating of service. 3. Clarify panel feeder size. 3/2 what? 1/2 what? 4. Provide fault calculations and fault current rating of panel. |
01/23/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/23/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY SEPERATED/NON-SEPERATED USE. 2) ALLOWABLE AREA FOR BUILDING HAS BEEN BASED ON F2 OCCUPANCY. CLARIFY THAT IS MOST RESTRICTIVE CLASSIFICATION FOR THIS BUILDING IF YOU ARE TRYING TO USE NON-SEPERATED USE PROVISIONS. CLARIFY ADJACENT TENANTS AND RATING OF DEMISING WALLS IF USING SEPERATED USE PROVISIONS. |
01/23/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |