Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM00220
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/23/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/23/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/16/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
03/16/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. The 2-way cleanout shown in the waste and vent diagram is in violation of Section 707.6, UPC 2003. See also Section 311.7, UPC 2003. 3. The added floor drain cannot be connected to the grease waste without a readily accessible (see definition of accessible in Section 203.0, UPC 2003.) flow control device between the trap vent and the grease trap. Reference Section 1014.3, UPC 2003. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/22/2007 | FSANCHE1 | OUT TO CUSTOMER | Completed |
03/22/2007 | SUE REEVES | REJECT SHELF | Completed |