Permit Number: T07CM00220
Parcel: 12108001B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM00220
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
02/23/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/16/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. The 2-way cleanout shown in the waste and vent diagram is in violation of Section 707.6, UPC 2003. See also Section 311.7, UPC 2003.
3. The added floor drain cannot be connected to the grease waste without a readily accessible (see definition of accessible in Section 203.0, UPC 2003.) flow control device between the trap vent and the grease trap. Reference Section 1014.3, UPC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/22/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/22/2007 SUE REEVES REJECT SHELF Completed